Abnormal Pressure Drop Rise: A Diagnostic Path from Ash Accumulation to Blockage

Aug 13, 2026 131 views ~7 min read Technical Knowledge
When the fan current quietly grows but the air volume shrinks, it is often the pressure drop alarming. This article gives the diagnostic path of "measure pressure drop → locate by segment → judge whether uniformly dirty or locally blocked," and distinguishes between online-treatable and shutdown-cleaning conditions.

I. Pressure Drop Is the "Blood Pressure" of the Heat Exchanger

Abnormal pressure drop rise means the flow channel is occupied. It often shares the same source as efficiency drop, but pressure drop is the more sensitive leading indicator—before it clogs enough to affect heat transfer, the current rises first.

II. Three Diagnostic Steps

  • Step 1: Measure total pressure drop. Compare with design value; a rise above 20% warrants inspection;
  • Step 2: Measure by segment. Add measurement points at heat exchanger inlet/outlet and between passes to lock down which segment rose;
  • Step 3: Judge the pattern. Uniform small rise across the line = general ash accumulation; sudden rise in one segment = local blockage/foreign object.

III. Common Sources

PhenomenonCauseTreatment
Uniform gas-side riseDust deposition, dirty filterPurge, replace filter (online possible)
Water-side riseScaling, biological slimeChemical/physical cleaning (mostly shutdown)
Sudden single-pass riseForeign object, plate deformationShutdown disassembly inspection

IV. Treatment Boundaries

  • Online: Back-blow, online brushing, filter replacement, no production stoppage;
  • Shutdown required: Plate disassembly high-pressure water, chemical soaking, scheduled in maintenance windows;
  • Prevention: Include pressure drop in daily inspection, set alarm threshold, don't wait for fan trip.
Treat pressure drop like blood pressure: measure daily, treat early, and the heat exchanger's life and efficiency both last longer.