+1(915)295-3666 kuns913@gmail.com 中文

Air-to-Air Plate Heat Exchanger Sizing Example (LMTD Method)

Aug 13, 2026 122 views ~6 min read Technical Knowledge
Theory is no match for a hands-on calculation. Using a drying exhaust recovery line as an example, this article starts from air volume and temperature and uses the LMTD method to step-by-step calculate the required heat transfer area, with complete formulas and values you can directly apply to your project.

I. Known Conditions

ParameterHot side (exhaust)Cold side (make-up air)
Air volume12000 m³/h12000 m³/h
Inlet temperature140°C20°C
Outlet temperature (target)90°C70°C
Air density (mean temp)≈ 0.95 kg/m³
Specific heat cp≈ 1.005 kJ/kg·K

II. Calculate Mass Flow and Recovered Heat

Mass flow m = (12000/3600) × 0.95 ≈ 3.17 kg/s. Cold side temperature rise 70−20 = 50 K:

Q = m·cp·ΔT = 3.17 × 1005 × 50 ≈ 159 kW

Hot side temperature drop 140−90 = 50 K, releasing the same 159 kW; energy balance is self-consistent.

III. Calculate LMTD (Counter Flow)

Counter-flow end temperature differences: ΔT₁ = 140−70 = 70 K, ΔT₂ = 90−20 = 70 K.

ΔTm = (70 − 70) / ln(70/70) → ends equal, so ΔTm = 70 K

In this example the two end temperature differences happen to be equal, a simplification of the symmetric condition.

IV. Calculate the Required Area

Take the overall heat transfer coefficient of the air-to-air plate heat exchanger K ≈ 25 W/m²·K (including two-side convection and thin wall):

A = Q / (K · ΔTm) = 159000 / (25 × 70) ≈ 90.9 m²

Adding a 10%~15% margin, select a plate pack of about 100 m². This result can be taken directly for quotation or to check equipment samples.

Selection is not guessing; it is settling the four accounts of Q, K, ΔTm, and A one by one.

Related Reading

Keywords: heat exchanger selection area calculation LMTD method air-to-air plate calculation example
Share: Weibo Twitter/X
← Previous
Metallurgy and Forging High-Temperat...
Next →
ε-NTU Method Heat Exchanger Check Ca...